Earth Coupled / Ground Source Pipe Loop Sizing

ECA PROGRAM OVERVIEW

The Elite Software Earth Coupled Analysis (ECA) Program quickly calculates the required pipe loop length necessary for heating and cooling a building with a given heat pump, soil, and weather conditions. ECA can analyze both vertical and horizontal pipe systems. In addition to computing pipe lengths, ECA can also generate a complete bill of materials with a cost estimate of the required labor and materials. Pressure losses through the equipment room, heat pump, header pipe, and the earth coil are computed along with the purge pressure and flow requirements. Heating and cooling runtime fractions are computed on a temperature bin basis. ECA is supplied with built-in data on many pipe types including polyethylene, polybutylene, copper, iron, and others. However, data on all pipe types can be revised and additional pipe types can be defined as well. Equivalent length data for fittings on all pipe types is also included. ECA comes with a heat pump data file containing performance data on models from several manufacturers. There is also provision for the user to add heat pump data from any other manufacturer. Data on all soil types listed in the ASHRAE manual are built-in to ECA, and the user can add more. Weather data for over 200 cities are built-in, and the weather data can be revised or added to as much as desired.

DEMONSTRATION DISKS

If you would like to evaluate the ECA program in further detail you can download a demonstration copy from our website, or order a copy, with complete documentation. The demonstration copies retain all the functionality of the full programs, they are just limited on the size of the project data that can be entered. Please follow this link for a description of the demonstration limits for the ECA program.

PROGRAM OUTPUT

The ECA Program provides the following four basic output reports: general project data, pipe length calculations, bill of materials, and pressure drop calculations. In addition to these reports the built-in pipe data, fitting data, and soil data can be printed. The user can specify exactly what reports are to be printed, the left hand margin, and starting page number. All reports can be printed to the screen or printer.

ECA FEATURES

  • Calculates Pipe Loop Lengths and Pressure Drops
  • Handles Both Horizontal and Vertical Systems
  • Prints Bill of Materials with Material and Labor Costs
  • Computes Minimum Purge GPM and Pressure
  • Follows OSU and ASHRAE Calculation Procedures
  • References Built-in Heat Pump Data
  • References Built-in Weather Data on over 200 Cities
  • Supplied with Data on All Common Soil Types
  • References Built-in Pipe and Fitting Data
  • Full Screen Input and Editing Features
  • Electronic Mouse Support
  • Instantaneous Input Error Checking
  • Disk Storage and Retrieval of All Input Data

CALCULATION METHOD

The ECA Program follows the methodology described in the Design/Data Manual for Closed-Loop Ground-Coupled Heat Pump Systems published by the American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE). All results computed by the program can be easily verified by hand to be in accordance with ASHRAE.

PROGRAM INPUT

The ECA program uses full screen editing features that provide a simple "fill in the blank" input procedure. All input data is checked at the time of entry so that no improper data can be entered. If you have a question about what the program is requesting, you can press the "?" key or F10 key which allows the program to offer additional explanations about the input data being requested. Upon completion of the input process, all data is saved to disk and can be reviewed and edited whenever desired. Two types of data are requested: general project data and specific system data. The general project data includes the project name and location, client and designer names, the building heating and cooling loads, the summer and winter design conditions, and the soil thermal properties. The system data includes the system type (vertical or horizontal), pipe material, pipe sizes, fitting data, antifreeze percentage, minimum and maximum entering water temperatures, series or parallel flow, and heat pump capacity, COP and EER values. Much of the input data for the heat pump, soil and weather conditions, and pipe materials can be automatically looked up by ECA. Input sheets are provided for the easy organization of your data.

SYSTEM REQUIREMENTS

ECA requires an IBM compatible computer with at least 640K of memory and DOS 5.0 or higher operating system. The computer must have floppy drives or a hard disk drive.


SAMPLE REPORT 1



YOUR   COMPANY         NAME              PROJECT NAME:      EXAMPLE PROJET

YOUR   COMPANY         TYPE              CLIENT  NAME:  MR. AND MRS. JONES

YOUR   CITY/STATE  LOCATION              DATE:           NOVEMBER 15, 1988



EARTH COUPLED ANALYSIS PROGRAM           DESIGNER:               YOUR NAME





GENERAL PROJECT INFORMATION:                                              



PROJECT LOCATION:                        TOMBALL (TOWN NEAR HOUSTON)      

CITY REFERENCE LOCATION:                 HOUSTON, TX                      

GENERAL COMMENT:                         VERTICAL SYSTEM                  

FLUID TYPE:                              WATER                            



FLUID DENSITY:                                62.37 LBS/CU.FT             

FLUID VISCOSITY:                               2.72 LBS/HR-FT             

MINIMUM PURGE VELOCITY:                        2.00 FT/SEC                





GENERAL COSTS:                                                            



DRILLING COST PER FOOT:                       $6.00                       

TRENCHING COST PER FOOT:                      $1.50                       

CIRCULATING PUMP COST:                      $200.00                       

MISCELLANEOUS MATERIAL COSTS:               $700.00                       

MISCELLANEOUS LABOR COSTS:                  $700.00                       





HEATING LOADS:                                                            



BUILDING HEATING LOAD:                    13,800.00 BTUH                  

WINTER BALANCE TEMPERATURE:                   60.00 DEG.F                 

OUTDOOR DESIGN TEMPERATURE:                   20.00 DEG.F                 

INDOOR DESIGN  TEMPERATURE:                   70.00 DEG.F                 





COOLING LOADS:                                                            



BUILDING COOLING LOAD:                    16,700.00 BTUH                  

SUMMER BALANCE TEMPERATURE:                   70.00 DEG.F                 

OUTDOOR DESIGN TEMPERATURE:                  100.00 DEG.F                 

INDOOR DESIGN  TEMPERATURE:                   75.00 DEG.F                 





SOIL THERMAL PROPERTIES:                                                  



SOIL DESCRIPTION:                     Wet-Saturated                       

THERMAL CONDUCTIVITY:                         1.400 BTUH/FT-DEG.F         

THERMAL DIFFUSIVITY:                          0.040 FT^2/HR               

DENSITY:                                    117.000 LB/FT^3               

SPECIFIC HEAT:                                0.300 BTU/LB-DEG.F          


SAMPLE REPORT 2



*** EARTH COUPLED ANALYSIS PROGRAM  BY  ELITE SOFTWARE DEVELOPMENT INC. **

YOUR COMPANY NAME                                 YOUR CITY/STATE LOCATION

EXAMPLE PROJECT            NOVEMBER 15, 1988                        PAGE 2

***************** PIPE LENGTH CALCULATION REPORT (CONT) ******************





      HEATING RUN-TIME FRACTION             COOLING RUN-TIME FRACTION     



BIN  RANGE  MIDPT    TOT   REQ   ACT  BIN  RANGE  MIDPT    TOT   REQ   ACT

    (F)      LOAD    HRS   HRS   HRS      (F)      LOAD    HRS   HRS   HRS

 55  -  59   1035   96.0   4.2   4.3   95  -  99  15030   18.0  14.2  14.0

 50  -  54   2760  108.0  12.7  12.8   90  -  94  12247  106.0  68.3  67.1

 45  -  49   4485   98.0  18.7  18.9   85  -  89   9463  142.0  70.7  69.5

 40  -  44   6210   98.0  25.9  26.2   80  -  84   6680  153.0  53.8  52.9

 35  -  39   7935   70.0  23.6  23.9   75  -  79   3897  250.0  51.3  50.4

 30  -  34   9660   39.0  16.0  16.2   70  -  74   1113   68.0   4.0   3.9

 25  -  29  11385   16.0   7.8   7.8   65  -  69      0    5.0   0.0   0.0

 20  -  24  13110    6.0   3.3   3.4   60  -  64      0    1.0   0.0   0.0

 15  -  19  14835    2.0   1.3   1.3   55  -  59      0    0.0   0.0   0.0

                   –––––––––––––––––                     –––––––––––––––––

HEATING TOTAL:     747.0 113.5 114.8  COOLING TOTAL:     743.0 262.3 257.8

RUN-TIME FRACTION:       0.152 0.154  RUN-TIME FRACTION:       0.353 0.347







PIPE INFORMATION:                                                         



EARTH COIL TYPE:                             VERTICAL                     

PIPE DESCRIPTION:                          SDR 11 IPS                     

THERMAL CONDUCTIVITY OF THE PIPE:               0.226 BTUH/FT-DEG.F       

NOMINAL DIAMETER OF THE PIPE:                   0.750 INCHES              

INSIDE DIAMETER  OF THE PIPE:                   0.860 INCHES              

OUTSIDE DIAMETER OF THE PIPE:                   1.050 INCHES              

PIPE RESISTANCE:                                0.096 LFT-HR-DEG.F/BTU    

REYNOLDS NUMBER AT 2 GPM & 1.1 FPS:             6,535                     

NUMBER OF LOOPS PER BORE:                         1.0                     

VERTICAL EARTH COIL DEPTH:                      210.0 FEET                

EARTH COIL LENGTH PER TON OF HEATING:           200.4 FEET/TON            

TOTAL BORE LENGTH REQUIRED FOR HEATING:         391.3 FEET                

EARTH COIL LENGTH PER TON OF COOLING:           254.0 FEET/TON            

TOTAL BORE LENGTH REQUIRED FOR COOLING:         404.6 FEET                

TOTAL ACTUAL BORE LENGTH:                       420.0 FEET                

TOTAL REQUIRED PIPE LENGTH:                     809.1 FEET                

TOTAL ACTUAL PIPE LENGTH:                       840.0 FEET                


SAMPLE REPORT 3



*** EARTH COUPLED ANALYSIS PROGRAM  BY  ELITE SOFTWARE DEVELOPMENT INC. **

YOUR COMPANY NAME                                 YOUR CITY/STATE LOCATION

EXAMPLE PROJECT              NOVEMBER 15, 1988                      PAGE 3

********************* PIPE LENGTH CALCULATION REPORT *********************



LOCATION:                                     HOUSTON, TX                 

DEEP EARTH TEMPERATURE:                              70.6 DEG.F           

ANNUAL TEMPERATURE SWING:                            15.7 DEG.F           

LOWEST  EARTH TEMPERATURE AT 210 FEET:               70.6 DEG.F           

HIGHEST EARTH TEMPERATURE AT 210 FEET:               70.6 DEG.F           

PHASE CONSTANT:                                      33.0 DAYS            



SOIL DESCRIPTION:                           Wet-Saturated                 



THERMAL CONDUCTIVITY OF THE SOIL:                   1.400 BTUH/FT-DEG.F   

THERMAL DIFFUSIVITY:                                0.040 FT^2/HR         

SOIL RESISTANCE:                                    0.622 LFT-HR-DEG.F/BTU



HEAT PUMP DESCRIPTION:        FHP SGL PKG-HIGH EFF - HE19                 



CONTINUOUS HOURS OF OPERATION:                      2,400 HOURS           

WATER FLOW RATE:                                      4.0 GPM             

AIR FLOW RATE:                                        600 CFM             

GLYCOL PERCENTAGE:                                      0                 



TOTAL COOLING CAPACITY:                            17,459 BTUH            

SENSIBLE COOLING CAPACITY:                         13,093 BTUH            

HEAT OF REJECTION:                                 23,903 BTUH            

COOLING INPUT POWER:                                1,781 WATTS           

CLG. LEAVING WATER TEMPERATURE:                    101.90 DEG.F           

COOLING COEFFICIENT OF PERFORMANCE:                 2.843                 

ENERGY EFFICIENCY RATIO (EER):                        9.7                 

MAXIMUM ENTERING WATER TEMPERATURE:                  90.0 DEG.F           



TOTAL HEATING CAPACITY:                            20,931 BTUH            

HEAT OF ABSORPTION:                                15,590 BTUH            

HEATING INPUT POWER:                                1,558 WATTS           

HTG. LEAVING WATER TEMPERATURE:                     54.20 DEG.F           

HEATING COEFFICIENT OF PERFORMANCE:                 3.900                 

MINIMUM ENTERING WATER TEMPERATURE:                  62.0 DEG.F           



PRESSURE DROP THROUGH HEAT PUMP:                    14.13 FEET OF HEAD    

STRIP HEAT:                                         0.000 KW              

STRIP ENERGY HEAT:                                  0.000 KWH             



REQUIRED TOTAL COOLING CAPACITY:                   19,000 BTUH            

REQUIRED TOTAL HEATING CAPACITY:                   23,500 BTUH            

REQUIRED EER OF COOLING:                           11.100                 

REQUIRED COP OF HEATING:                            4.000                 

ACTUAL   TOTAL COOLING CAPACITY:                   19,333 BTUH            

ACTUAL   TOTAL HEATING CAPACITY:                   23,240 BTUH            

MAXIMUM  TOTAL COOLING CAPACITY:                   19,333 BTUH            

MINIMUM  TOTAL HEATING CAPACITY:                   23,240 BTUH            



PRESSURE DROP CALCULATIONS:                                               



LOOP SYSTEM TYPE:                              PARALLEL                   

LOOP SYSTEM PIPE TYPE:                         SDR 11 IPS                 

LOOP SYSTEM PIPE LENGTH:                           840.00 FEET            

LOOP SYSTEM PIPE DIAMETER:                           0.75 INCHES          



EQUIPMENT ROOM DROP:                                 1.65 FEET OF HEAD    

HEAT PUMP DROP:                                     19.50 FEET OF HEAD    

HEADER PIPE DROP:                                    0.31 FEET OF HEAD    

SINGLE LOOP SYSTEM DROP:                             4.01 FEET OF HEAD    



TOTAL SYSTEM DROP:                                  25.47 FEET OF HEAD    



TOTAL FLUID IN SYSTEM:                              34.97 GALLONS         



SYSTEM PURGE FLOW:                                  12.69 GAL. PER MIN    

SYSTEM PURGE PRESSURE:                              32.58 FEET OF HEAD    

MINIMUM PURGE VELOCITY:                              2.00 FEET PER SEC    


SAMPLE REPORT 4



*** EARTH COUPLED ANALYSIS PROGRAM  BY  ELITE SOFTWARE DEVELOPMENT INC. **

YOUR COMPANY NAME                                 YOUR CITY/STATE LOCATION

EXAMPLE PROJECT              NOVEMBER 15, 1988                      PAGE 4

************************ BILL OF MATERIALS REPORT ************************



PIPE COSTS:                                                               



PIPE                 PIPE  PIPE    MATER. LABOR     TOTAL   TOTAL    TOTAL

MATERIAL             SIZE  LENGTH  COST   COST      MATER   LABOR    M&LAB

DESCRIPTION          (IN)  (FEET)  PER.FT PER.FT    COSTS   COSTS    COSTS



EQ: SCH 40 IPS       1.00     120    0.50   0.20    60.00   24.00    84.00

HD: SCH 40 IPS       1.50      40    0.90   0.20    36.00    8.00    44.00

ER: SDR 11 IPS       0.75     840    0.30   0.10   252.00   84.00   336.00

                            -----                 ------- -------  -------

TOTALS:                     1,000                 $348.00 $116.00  $464.00





FITTING COSTS:                                                            



PIPE                 FIT.   NUM.   MATER. LABOR     TOTAL   TOTAL    TOTAL

FITTING              SIZE   OF     COST/  COST/     MATER   LABOR    M&LAB

DESCRIPTION          (IN)   FITS   FITTNG FITTNG    COSTS   COSTS    COSTS



EQ: Regular 90^ Elb  1.00     4      3.00   0.50    12.00    2.00    14.00

HD: Regular 90^ Elb  1.50     4      5.00   0.70    20.00    2.80    22.80

HD: Straight Ser. S  1.50     4      7.50   1.40    30.00    5.60    35.60

HD: Reducer          1.50     2      9.00   0.50    18.00    1.00    19.00

ER: U-bend           0.75     3     17.50   1.50    52.50    4.50    57.00

ER: Regular 90^ Elb  0.75     2      2.00   0.40     4.00    0.80     4.80

                            ---                   -------  ------  -------

TOTALS:                      19                   $136.50  $16.70  $153.20





BILL OF MATERIALS REPORT SUMMARY:             MATERIAL     LABOR     TOTAL



TOTAL PIPE COSTS:                               348.00    116.00    464.00

TOTAL PIPE FITTING COSTS:                       136.50     16.70    153.20

DRILLING COSTS:                                   0.00   2520.00   2520.00

CIRCULATING PUMP COST:                          200.00      0.00    200.00

FHP SGL PKG-HIGH EFF - HE19 HEAT PUMP:            0.00      0.00      0.00

MISCELLANEOUS COSTS:                            700.00    700.00   1400.00

                                                  ----      ----      ----

TOTAL MATERIAL, LABOR, & PROJECT COSTS:     $1,384.50 $3,352.70 $4,737.220