ECA PROGRAM OVERVIEWThe Elite Software Earth Coupled Analysis (ECA) Program quickly calculates the required pipe loop length necessary for heating and cooling a building with a given heat pump, soil, and weather conditions. ECA can analyze both vertical and horizontal pipe systems. In addition to computing pipe lengths, ECA can also generate a complete bill of materials with a cost estimate of the required labor and materials. Pressure losses through the equipment room, heat pump, header pipe, and the earth coil are computed along with the purge pressure and flow requirements. Heating and cooling runtime fractions are computed on a temperature bin basis. ECA is supplied with built-in data on many pipe types including polyethylene, polybutylene, copper, iron, and others. However, data on all pipe types can be revised and additional pipe types can be defined as well. Equivalent length data for fittings on all pipe types is also included. ECA comes with a heat pump data file containing performance data on models from several manufacturers. There is also provision for the user to add heat pump data from any other manufacturer. Data on all soil types listed in the ASHRAE manual are built-in to ECA, and the user can add more. Weather data for over 200 cities are built-in, and the weather data can be revised or added to as much as desired. DEMONSTRATION DISKSIf you would like to evaluate the ECA program in further detail you can download a demonstration copy from our website, or order a copy, with complete documentation. The demonstration copies retain all the functionality of the full programs, they are just limited on the size of the project data that can be entered. Please follow this link for a description of the demonstration limits for the ECA program. PROGRAM OUTPUTThe ECA Program provides the following four basic output reports: general project data, pipe length calculations, bill of materials, and pressure drop calculations. In addition to these reports the built-in pipe data, fitting data, and soil data can be printed. The user can specify exactly what reports are to be printed, the left hand margin, and starting page number. All reports can be printed to the screen or printer. |
ECA FEATURES
CALCULATION METHODThe ECA Program follows the methodology described in the Design/Data Manual for Closed-Loop Ground-Coupled Heat Pump Systems published by the American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE). All results computed by the program can be easily verified by hand to be in accordance with ASHRAE. PROGRAM INPUTThe ECA program uses full screen editing features that provide a simple "fill in the blank" input procedure. All input data is checked at the time of entry so that no improper data can be entered. If you have a question about what the program is requesting, you can press the "?" key or F10 key which allows the program to offer additional explanations about the input data being requested. Upon completion of the input process, all data is saved to disk and can be reviewed and edited whenever desired. Two types of data are requested: general project data and specific system data. The general project data includes the project name and location, client and designer names, the building heating and cooling loads, the summer and winter design conditions, and the soil thermal properties. The system data includes the system type (vertical or horizontal), pipe material, pipe sizes, fitting data, antifreeze percentage, minimum and maximum entering water temperatures, series or parallel flow, and heat pump capacity, COP and EER values. Much of the input data for the heat pump, soil and weather conditions, and pipe materials can be automatically looked up by ECA. Input sheets are provided for the easy organization of your data. SYSTEM REQUIREMENTSECA requires an IBM compatible computer with at least 640K of memory and DOS 5.0 or higher operating system. The computer must have floppy drives or a hard disk drive. |
YOUR COMPANY NAME PROJECT NAME: EXAMPLE PROJET YOUR COMPANY TYPE CLIENT NAME: MR. AND MRS. JONES YOUR CITY/STATE LOCATION DATE: NOVEMBER 15, 1988 EARTH COUPLED ANALYSIS PROGRAM DESIGNER: YOUR NAME GENERAL PROJECT INFORMATION: PROJECT LOCATION: TOMBALL (TOWN NEAR HOUSTON) CITY REFERENCE LOCATION: HOUSTON, TX GENERAL COMMENT: VERTICAL SYSTEM FLUID TYPE: WATER FLUID DENSITY: 62.37 LBS/CU.FT FLUID VISCOSITY: 2.72 LBS/HR-FT MINIMUM PURGE VELOCITY: 2.00 FT/SEC GENERAL COSTS: DRILLING COST PER FOOT: $6.00 TRENCHING COST PER FOOT: $1.50 CIRCULATING PUMP COST: $200.00 MISCELLANEOUS MATERIAL COSTS: $700.00 MISCELLANEOUS LABOR COSTS: $700.00 HEATING LOADS: BUILDING HEATING LOAD: 13,800.00 BTUH WINTER BALANCE TEMPERATURE: 60.00 DEG.F OUTDOOR DESIGN TEMPERATURE: 20.00 DEG.F INDOOR DESIGN TEMPERATURE: 70.00 DEG.F COOLING LOADS: BUILDING COOLING LOAD: 16,700.00 BTUH SUMMER BALANCE TEMPERATURE: 70.00 DEG.F OUTDOOR DESIGN TEMPERATURE: 100.00 DEG.F INDOOR DESIGN TEMPERATURE: 75.00 DEG.F SOIL THERMAL PROPERTIES: SOIL DESCRIPTION: Wet-Saturated THERMAL CONDUCTIVITY: 1.400 BTUH/FT-DEG.F THERMAL DIFFUSIVITY: 0.040 FT^2/HR DENSITY: 117.000 LB/FT^3 SPECIFIC HEAT: 0.300 BTU/LB-DEG.F
*** EARTH COUPLED ANALYSIS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC. ** YOUR COMPANY NAME YOUR CITY/STATE LOCATION EXAMPLE PROJECT NOVEMBER 15, 1988 PAGE 2 ***************** PIPE LENGTH CALCULATION REPORT (CONT) ****************** HEATING RUN-TIME FRACTION COOLING RUN-TIME FRACTION BIN RANGE MIDPT TOT REQ ACT BIN RANGE MIDPT TOT REQ ACT (F) LOAD HRS HRS HRS (F) LOAD HRS HRS HRS 55 - 59 1035 96.0 4.2 4.3 95 - 99 15030 18.0 14.2 14.0 50 - 54 2760 108.0 12.7 12.8 90 - 94 12247 106.0 68.3 67.1 45 - 49 4485 98.0 18.7 18.9 85 - 89 9463 142.0 70.7 69.5 40 - 44 6210 98.0 25.9 26.2 80 - 84 6680 153.0 53.8 52.9 35 - 39 7935 70.0 23.6 23.9 75 - 79 3897 250.0 51.3 50.4 30 - 34 9660 39.0 16.0 16.2 70 - 74 1113 68.0 4.0 3.9 25 - 29 11385 16.0 7.8 7.8 65 - 69 0 5.0 0.0 0.0 20 - 24 13110 6.0 3.3 3.4 60 - 64 0 1.0 0.0 0.0 15 - 19 14835 2.0 1.3 1.3 55 - 59 0 0.0 0.0 0.0 ––––––––––––––––– ––––––––––––––––– HEATING TOTAL: 747.0 113.5 114.8 COOLING TOTAL: 743.0 262.3 257.8 RUN-TIME FRACTION: 0.152 0.154 RUN-TIME FRACTION: 0.353 0.347 PIPE INFORMATION: EARTH COIL TYPE: VERTICAL PIPE DESCRIPTION: SDR 11 IPS THERMAL CONDUCTIVITY OF THE PIPE: 0.226 BTUH/FT-DEG.F NOMINAL DIAMETER OF THE PIPE: 0.750 INCHES INSIDE DIAMETER OF THE PIPE: 0.860 INCHES OUTSIDE DIAMETER OF THE PIPE: 1.050 INCHES PIPE RESISTANCE: 0.096 LFT-HR-DEG.F/BTU REYNOLDS NUMBER AT 2 GPM & 1.1 FPS: 6,535 NUMBER OF LOOPS PER BORE: 1.0 VERTICAL EARTH COIL DEPTH: 210.0 FEET EARTH COIL LENGTH PER TON OF HEATING: 200.4 FEET/TON TOTAL BORE LENGTH REQUIRED FOR HEATING: 391.3 FEET EARTH COIL LENGTH PER TON OF COOLING: 254.0 FEET/TON TOTAL BORE LENGTH REQUIRED FOR COOLING: 404.6 FEET TOTAL ACTUAL BORE LENGTH: 420.0 FEET TOTAL REQUIRED PIPE LENGTH: 809.1 FEET TOTAL ACTUAL PIPE LENGTH: 840.0 FEET
*** EARTH COUPLED ANALYSIS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC. ** YOUR COMPANY NAME YOUR CITY/STATE LOCATION EXAMPLE PROJECT NOVEMBER 15, 1988 PAGE 3 ********************* PIPE LENGTH CALCULATION REPORT ********************* LOCATION: HOUSTON, TX DEEP EARTH TEMPERATURE: 70.6 DEG.F ANNUAL TEMPERATURE SWING: 15.7 DEG.F LOWEST EARTH TEMPERATURE AT 210 FEET: 70.6 DEG.F HIGHEST EARTH TEMPERATURE AT 210 FEET: 70.6 DEG.F PHASE CONSTANT: 33.0 DAYS SOIL DESCRIPTION: Wet-Saturated THERMAL CONDUCTIVITY OF THE SOIL: 1.400 BTUH/FT-DEG.F THERMAL DIFFUSIVITY: 0.040 FT^2/HR SOIL RESISTANCE: 0.622 LFT-HR-DEG.F/BTU HEAT PUMP DESCRIPTION: FHP SGL PKG-HIGH EFF - HE19 CONTINUOUS HOURS OF OPERATION: 2,400 HOURS WATER FLOW RATE: 4.0 GPM AIR FLOW RATE: 600 CFM GLYCOL PERCENTAGE: 0 TOTAL COOLING CAPACITY: 17,459 BTUH SENSIBLE COOLING CAPACITY: 13,093 BTUH HEAT OF REJECTION: 23,903 BTUH COOLING INPUT POWER: 1,781 WATTS CLG. LEAVING WATER TEMPERATURE: 101.90 DEG.F COOLING COEFFICIENT OF PERFORMANCE: 2.843 ENERGY EFFICIENCY RATIO (EER): 9.7 MAXIMUM ENTERING WATER TEMPERATURE: 90.0 DEG.F TOTAL HEATING CAPACITY: 20,931 BTUH HEAT OF ABSORPTION: 15,590 BTUH HEATING INPUT POWER: 1,558 WATTS HTG. LEAVING WATER TEMPERATURE: 54.20 DEG.F HEATING COEFFICIENT OF PERFORMANCE: 3.900 MINIMUM ENTERING WATER TEMPERATURE: 62.0 DEG.F PRESSURE DROP THROUGH HEAT PUMP: 14.13 FEET OF HEAD STRIP HEAT: 0.000 KW STRIP ENERGY HEAT: 0.000 KWH REQUIRED TOTAL COOLING CAPACITY: 19,000 BTUH REQUIRED TOTAL HEATING CAPACITY: 23,500 BTUH REQUIRED EER OF COOLING: 11.100 REQUIRED COP OF HEATING: 4.000 ACTUAL TOTAL COOLING CAPACITY: 19,333 BTUH ACTUAL TOTAL HEATING CAPACITY: 23,240 BTUH MAXIMUM TOTAL COOLING CAPACITY: 19,333 BTUH MINIMUM TOTAL HEATING CAPACITY: 23,240 BTUH PRESSURE DROP CALCULATIONS: LOOP SYSTEM TYPE: PARALLEL LOOP SYSTEM PIPE TYPE: SDR 11 IPS LOOP SYSTEM PIPE LENGTH: 840.00 FEET LOOP SYSTEM PIPE DIAMETER: 0.75 INCHES EQUIPMENT ROOM DROP: 1.65 FEET OF HEAD HEAT PUMP DROP: 19.50 FEET OF HEAD HEADER PIPE DROP: 0.31 FEET OF HEAD SINGLE LOOP SYSTEM DROP: 4.01 FEET OF HEAD TOTAL SYSTEM DROP: 25.47 FEET OF HEAD TOTAL FLUID IN SYSTEM: 34.97 GALLONS SYSTEM PURGE FLOW: 12.69 GAL. PER MIN SYSTEM PURGE PRESSURE: 32.58 FEET OF HEAD MINIMUM PURGE VELOCITY: 2.00 FEET PER SEC
*** EARTH COUPLED ANALYSIS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC. ** YOUR COMPANY NAME YOUR CITY/STATE LOCATION EXAMPLE PROJECT NOVEMBER 15, 1988 PAGE 4 ************************ BILL OF MATERIALS REPORT ************************ PIPE COSTS: PIPE PIPE PIPE MATER. LABOR TOTAL TOTAL TOTAL MATERIAL SIZE LENGTH COST COST MATER LABOR M&LAB DESCRIPTION (IN) (FEET) PER.FT PER.FT COSTS COSTS COSTS EQ: SCH 40 IPS 1.00 120 0.50 0.20 60.00 24.00 84.00 HD: SCH 40 IPS 1.50 40 0.90 0.20 36.00 8.00 44.00 ER: SDR 11 IPS 0.75 840 0.30 0.10 252.00 84.00 336.00 ----- ------- ------- ------- TOTALS: 1,000 $348.00 $116.00 $464.00 FITTING COSTS: PIPE FIT. NUM. MATER. LABOR TOTAL TOTAL TOTAL FITTING SIZE OF COST/ COST/ MATER LABOR M&LAB DESCRIPTION (IN) FITS FITTNG FITTNG COSTS COSTS COSTS EQ: Regular 90^ Elb 1.00 4 3.00 0.50 12.00 2.00 14.00 HD: Regular 90^ Elb 1.50 4 5.00 0.70 20.00 2.80 22.80 HD: Straight Ser. S 1.50 4 7.50 1.40 30.00 5.60 35.60 HD: Reducer 1.50 2 9.00 0.50 18.00 1.00 19.00 ER: U-bend 0.75 3 17.50 1.50 52.50 4.50 57.00 ER: Regular 90^ Elb 0.75 2 2.00 0.40 4.00 0.80 4.80 --- ------- ------ ------- TOTALS: 19 $136.50 $16.70 $153.20 BILL OF MATERIALS REPORT SUMMARY: MATERIAL LABOR TOTAL TOTAL PIPE COSTS: 348.00 116.00 464.00 TOTAL PIPE FITTING COSTS: 136.50 16.70 153.20 DRILLING COSTS: 0.00 2520.00 2520.00 CIRCULATING PUMP COST: 200.00 0.00 200.00 FHP SGL PKG-HIGH EFF - HE19 HEAT PUMP: 0.00 0.00 0.00 MISCELLANEOUS COSTS: 700.00 700.00 1400.00 ---- ---- ---- TOTAL MATERIAL, LABOR, & PROJECT COSTS: $1,384.50 $3,352.70 $4,737.220