Industrial Ventilation and Exhaust

VENT PROGRAM OVERVIEW

The Elite Software VENT program analyzes industrial ventilation and exhaust duct systems. With VENT, optimal duct sizes can be determined that maintain both the minimum desired velocity and balanced static pressures at all duct junctions. VENT can work with both round and rectangular ducts of any duct material desired. VENT has provision for virtually all types of components found in ventilation and exhaust systems including: ductwork, hoods, fans, collectors, blast gates, system effect factors, and all types of fittings. Hoods can be selectively designed with any slot dimensions desired. Collectors can be specified as fabric filter, mechanical, electrostatic, wet, or as a combined fan and collector. VENT can also calculate the effect of temperature changes and moisture addition/removal that dryers, wet collectors, and other such items might have on the air. Essentially, VENT can be instructed to work with standard sea level air or to adjust air quantities and properties as dictated by the psychrometric air conditions. In achieving balanced static pressures at junctions, VENT allows the designer to quickly experiment with the effects of changing a duct size, fitting type, branch entry angle, hood data, or even a blast gate. VENT allows the designer to decide on the preferred way of balancing static pressures for each junction. VENT even provides the option of adjusting the cfm values of converging duct sections to achieve a static pressure balance. VENT calculates extremely fast and performs extensive error checking of the exhaust duct system.

PROGRAM INPUT

VENT uses full screen editing features that provide a simple "fill in the blank" data entry procedure. All input data is checked at the time of entry so that no improper data can be entered. If you have a question about what the program is requesting, you can press the "?" or F10 key to obtain additional help explanations. All data is saved to disk as it is entered. Five major types of data are requested: General Project Information, Ducts, Hoods, Collectors, and Fans. The general project data includes the date, project location, client, designer, and project name, the elevation, room conditions, duct material data, and fitting database. Duct section data must be given beginning and ending node numbers, shape (round or rectangular), dimensions, and lengths. A duct section can include any combination of duct runs and fittings. Hoods, collectors, and fans are entered as occurring at a particular node number. Hoods require a design cfm, duct entry loss factor, minimum duct velocity, slot data, and additional loss data. Collectors require the collector type (fabric, mechanical, electrostatic, wet, or fan/collector), design pressure drop, design flow rate, duct reentry loss factor, and minimum outlet velocity. Fans require entry of the inlet diameter, outlet area, fan speed, blast to outlet area ratio, outlet elbow direction, and fan performance data concerning static pressure and cfm values. Alternatively, VENT can compute required fan properties and use those directly.

VENT FEATURES

  • Analyzes Industrial ventilation & Exhaust Duct Systems
  • Sizes Both Round and Rectangular Ductwork
  • Calculates Flows, Velocities, Pressures, & Temperatures
  • Helps Achieve Balanced Static Pressures at Junctions
  • Allows Up to 200 Hoods and 400 Duct Sections
  • Allows Up to 50 Fans and 50 Collectors
  • Handles All types of Fittings and Branch Entry Losses
  • Helps Size Hoods and Slot Dimensions
  • Accounts for Non-Standard Air Conditions
  • Full Screen Input and Editing Features
  • Electronic Mouse Support
  • Instantaneous Input Error Checking
  • Provides Comprehensive and Concise Reports

CALCULATION METHOD

VENT uses the design methods and data explained in the ACGIH Industrial ventilation Manual, 20th edition. All output report results can be easily verified by hand.

PROGRAM OUTPUT

The VENT Program provides both input and output reports. The input reports lists the general project data and all the specific data for duct sections, hoods, collectors, and fans. The general project data report shows the date, project location, client, designer, and project name, the elevation, room conditions, duct material data, and fitting database. The hood data report shows the hood air flow and velocity (corrected for psychrometric conditions if desired), and all slot data (velocity, dimensions, and area) if slots were used. The duct section output report shows computed duct dimensions, air flow quantities and velocities, static pressure losses, available static and velocity pressures, and all blast gate data if one was selected. The fan output data includes the flow rate at the fan inlet, the density of the air at the fan inlet, the required fan total and static pressures, and the air horsepower required. The user can specify exactly what reports to print, and all reports can be printed to the screen, printer, or to an ASCII disk file. Options are provided for specifying the starting page number and left hand margin.

DEMONSTRATION DISKS

If you would like to evaluate the VENT program in further detail you can download a demonstration copy from our website, or order a copy, with complete documentation. The demonstration copies retain all the functionality of the full programs, they are just limited on the size of the project data that can be entered. Please follow this link for a description of the demonstration limits for the VENT program.

SYSTEM REQUIREMENTS

VENT requires an IBM compatible computer with at least 640K of memory and DOS 5.0 or higher. The computer must have either two floppy disk drives or a hard disk drive.


SAMPLE REPORT 1


YOUR      COMPANY       NAME              PROJECT:          SAMPLE PROJECT
YOUR      COMPANY       TYPE              CLIENT:     JOHN DOE ENTERPRISES
YOUR CITY AND STATE LOCATION              DATE:              AUGUST 1,1994

INDUSTRIAL VENTILATION PROGRAM            DESIGNER:             W.W. SMITH


GENERAL PROJECT DATA:                                                     
                                                                          
MATERIAL ROUGHNESS:                      0.00050 Ks                       
ELBOW DATABASE:                      VENT MANUAL                          
ROOM PRESSURE:                            14.700 PSIA                     
ROOM NEGATIVE PRESSURE:                    0.000 WG                       
USE PSYCHROMETRICS:                           NO                          
ELEVATION:                                  0.00 FT                       
DRY BULB TEMPERATURE:                     70.000 F                        

SECOND PSYCHROMETRIC VARIABLE:              NONE                          
SECOND PSYCHROMETRIC VALUE:                 NONE                          

ROUND DUCT MAXIMUM SIZES:          6    20  9999 INCHES                   
ROUND DUCT INCREMENT:            0.5   1.0   2.0 INCHES                   

RECTANGULAR DUCT MAXIMUM SIZES:             9999 INCHES                   
RECTANGULAR DUCT INCREMENT:                  1.0 INCHES                   


HOOD INPUT DATA:                                                          

HD HOOD  AIR AIR PSYCH DUCT ENTRY SLOT OTH  ADD  SLOT NO. SLOT  SLOT SLOT 
NO.FLOW  TYP TMP -VAR-  VEL  LOSS FACT LOSS LOSS  VEL SLT WID.  LEN. SQ.IN

1  1800 SCFM  70  NONE 3500  0.25 1.78  0.0  0.0  N/A   3 1.50 30.00 135.0

2  1250 SCFM  70  NONE 4000  0.25 1.78  0.0  0.0  N/A N/A 0.00  0.00  86.4

3   610 SCFM  70  NONE 4500  0.40 0.00  0.0  0.0  N/A N/A 0.00  0.00   0.0

4   610 SCFM  70  NONE 4500  0.40 0.00  0.0  0.0  N/A N/A 0.00  0.00   0.0

5   610 SCFM  70  NONE 4500  0.40 0.00  0.0  0.0  N/A N/A 0.00  0.00   0.0

6   610 SCFM  70  NONE 4500  0.40 0.00  0.0  0.0  N/A N/A 0.00  0.00   0.0

7  1800 SCFM  70  NONE 3500  0.25 1.78  0.0  0.0  N/A   3 1.50 30.00 135.0

8   610 SCFM  70  NONE 4500  0.40 0.00  0.0  0.0  N/A N/A 0.00  0.00   0.0

9   610 SCFM  70  NONE 4500  0.40 0.00  0.0  0.0  N/A N/A 0.00  0.00   0.0


COLLECTOR INPUT DATA:                                                     

COLL   COLL     DESIGN    DESIGN    REENTRY    EXP.FOR    MIN.VEL         
NODE   TYPE     P.DROP      FLOW       LOSS    SP.VS.Q    AFTER.COLL      

/C     FABRIC   3.5 WG      9000       0.50       1.50          2500      



FAN INPUT DATA:                                                           

FAN    INLET    OUTLET    FAN     BLAST.TO     OUTLET      FAN            
NODE   DIA.     AREA      SPEED   OUTLET       ELBOW       IDENTIFICATION 
NO.    INCHES   INCHES    -RPM-   AREA.RATIO   DIRECTION   DESCRIPTION    

#F     *********** SPECIFIED TO USE PROGRAM COMPUTED DATA ************    


SAMPLE REPORT 2


**** INDUSTRIAL VENTILATION PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC ****
YOUR COMPANY NAME                                         YOUR CITY, STATE
SAMPLE PROJECT                AUGUST 1, 1994                        PAGE 2
**************************** VENT OUTPUT DATA ****************************

DUCT SECTION OUTPUT DATA:                                                 

BEG  END  DUCT  HT/DIA    AREA DES.CFM DCT.VEL DCT.VP HD.SCT  DUCT  S.PRES
NODE NODE SHAPE  WIDTH  GOV.SP COR.CFM BG.DPTH  BG.LS VEL.PR  LOSS  AT.END

1    -A   ROUND  9.000  0.4418    1800    4074   1.03   2.21  1.32   -3.54
                 0.000   -3.71    1843    0.00   0.00   0.00              

2    -A   ROUND  7.000  0.2673    1250    4677   1.36   2.19  1.52   -3.71
                 0.000   -3.71    1250    0.00   0.00   0.00              

A    -B   ROUND 12.000  0.7854    3093    3938   0.97   0.00  0.26   -3.97
                 0.000   -3.97    3093    0.00   0.00   0.00              

3    -D   ROUND  5.000  0.1364     610    4474   1.25   1.75  0.50   -2.25
                 0.000   -2.25     610    0.00   0.00   0.00              

4    -D   ROUND  5.000  0.1364     610    4474   1.25   1.75  0.50   -2.25
                 0.000   -2.25     610    0.00   0.00   0.00              

D    -B   ROUND  7.000  0.2673    1220    4565   1.30   0.00  1.14   -3.44
                 0.000   -3.97    1310    0.00   0.00   0.00              

B    -C   ROUND 13.000  0.9218    4403    4777   1.42   0.00  0.46   -4.76
                 0.000   -4.76    4403    0.00   0.00   0.00              

5    -E   ROUND  5.000  0.1364     610    4474   1.25   1.75  0.50   -2.25
                 0.000   -2.25     610    0.00   0.00   0.00              

6    -E   ROUND  5.000  0.1364     610    4474   1.25   1.75  0.50   -2.25
                 0.000   -2.25     610    0.00   0.00   0.00              

E    -C   ROUND  7.000  0.2673    1220    4565   1.30   0.00  1.14   -3.44
                 0.000   -4.76    1220    2.79   1.31   0.00              

C    -/C  ROUND 15.000  1.2272    5623    4582   1.31   0.00  1.55   -6.31
                 0.000   -6.31    5623    0.00   0.00   0.00              

7    -F   ROUND  9.000  0.4418    1800    4074   1.03   2.21  1.38   -3.60
                 0.000   -3.60    1800    0.00   0.00   0.00              

9    -G   ROUND  5.000  0.1364     610    4474   1.25   1.75  0.50   -2.25
                 0.000   -2.25     610    0.00   0.00   0.00              

8    -G   ROUND  5.000  0.1364     610    4474   1.25   1.75  0.50   -2.25
                 0.000   -2.25     610    0.00   0.00   0.00              

G    -F   ROUND  7.000  0.2673    1220    4565   1.30   0.00  1.14   -3.44
                 0.000   -3.60    1247    0.00   0.00   0.00              

F    -H   ROUND 11.000  0.6600    3047    4617   1.33   0.00  0.13   -3.91
                 0.000   -3.91    3130    0.00   0.00   0.00              

H    -H   ROUND 10.000  0.5454    3047    5587   1.95   0.00  0.48   -5.00
                 0.000   -5.00    3130    0.00   0.00   0.00              

H    -/C  ROUND 11.000  0.6600    3047    4617   1.33   0.00  0.98   -5.98
                 0.000   -6.31    3130    0.00   0.00   0.00              


/C   -F   ROUND 24.000  3.1416    8753    2786   0.48   0.00  0.30  -10.69
                 0.000  -10.69    8753    0.00   0.00   0.00              


SAMPLE REPORT 3


**** INDUSTRIAL VENTILATION PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC ****
YOUR COMPANY NAME                                         YOUR CITY, STATE
SAMPLE PROJECT                AUGUST 1, 1994                        PAGE 3
**************************** VENT OUTPUT DATA ****************************


DUCT SECTION OUTPUT DATA:                                                 

BEG  END  DUCT  HT/DIA    AREA DES.CFM DCT.VEL DCT.VP HD.SCT  DUCT  S.PRES
NODE NODE SHAPE  WIDTH  GOV.SP COR.CFM BG.DPTH  BG.LS VEL.PR  LOSS  AT.END

#F   -+#F RECT  23.000  3.9931    8753    2192   0.30   0.00  0.01    0.53
                25.000    0.53    8753    0.00   0.00   0.00              

+#F  -LP  ROUND 22.000  2.6398    8753    3316   0.69   0.00  0.15    0.00
                 0.000    0.00    8753    0.00   0.00   0.00              



FAN OUTPUT DATA:                                                          

FAN NODE:                                #F                               
FLOWRATE AT FAN INLET:                 8753 CFM                           
FAN INLET DENSITY:                   0.0749 LBM PER CUBIC FOOT            
FAN STATIC PRESS W/O SYSTEM EFFECT:   10.93 WG                            
FAN TOTAL PRESS W/O SYSTEM EFFECT:    11.23 WG                            
AIR HORSEPOWER REQUIRED:               16.2 HP                            
AIR HORSEPOWER REQUIRED AT STD COND:   16.2 HP                            