Phase refers to
However, when you use only two of the legs of a 3-phase system, it is single phase since there is no
other phase that it is "out of phase" with. The term two-phase is a misnomer, although many
electricians use it. There is only ONE sine wave, hence it is single-phase.
>Also, where IS the neutral (Ok, return) line of 3 phase?
Well, that depends on the type of 3-phase system. A Delta configuration (230 or 460 Volts line-line)
doesn't have a neutral. It has a SAFETY GROUND, but that's different. One line returns to the next
line. When DELTA comes into a building, it then goes to a transformer where the winding across two of
the lines is center-tapped, producing 115 Volts from each line to that center-tap. The center-tap
becomes the neutral (return) for 115 V lighting circuits. Also, this neutral is connected to a good
earth-ground near the transformer.
[ ed. note - As you can see from the above, A,B, and C are equidistant, there for at the same potential to each other. A and C are equidistant to Neutral, at 115V each. B, however, is farther away from neutral ( whether on the path through a, or through C ), therefor a 'high leg'. ]
A WYE configuration is another matter. There is 208 Volts from line-to-line. There is 120 Volts from
line-to-neutral (208 V / 1.73 = 120 V). This is often called 120/208 V, 3-phase, 5-wire. The obvious
advantage is that you get three-120 V lines for lighting circuits as opposed to the two that you get
in the DELTA system above.
As far as I know, these are the two standards used in the United States today. It is important to
know exactly what you have. Whenever my company sells a refrigeration system, we ask if the customer
requires 208 or 230. We usually get a reply like, "Oh, 220V, whatever". Well, it makes a big
difference since most compressors (over 1/2 HP) are designed to work at 230 V nominal, no lower than
208 V. If the customer has a 208 V line that is on the low side, it can be as low as 187 V. That can
cause starting problems, causing the compressor to draw lock-rotor and never start! Also, some
systems require the neutral of a 208 V WYE to develop 120 V for the control circuits. If the customer
only has 230 V DELTA available, the machine must have an internal control transformer to develop 115
V (proper designed 208 V units should have an internal transformer too, but not everything is
properly designed).
There are only two true nominal values in the U.S. -- 115V (from a delta)
or 120V (from a wye). Anything else (110V, 220V) is a misnomer, based on
archaic nominal values from the 1920's and '30's.
BTW, The advantage of 208V for industrial sites is that you get three-120V
lines for lighting/appliance circuits, whereas with 230V you only get
two-115V lines.
The relationship of 208/120V is that the neutral is not a center tap. It is
the node where three phases come together. It is 208V divided by the
tangent of 60 degrees or 208V/1.73=120V.
Hope I haven't rambled too long. Feel free to post this elsewhere if you think it would be helpful to
others.
Peter Kesselman. Opinions are definitely my own.
B
*
* *
A * *:* * C
:
:
:
Neutral (Center-tap. Connected to earth-ground. Return for 115 V)
B * * C
* *
* *
*------- Neutral (Connected to earth-ground. Return for 120 V)
*
*
A
Back to Interesting Threads Index